The equivalent model of offshore DC power collection network for the harmonic susceptibility study is proposed based on the discrete time-domain modelling technique and frequency scan approach in the frequency domain. The proposed methodology for modelling a power converter and a DC collection system in the frequency domain can satisfy harmonic studies of any configuration of wind farm network and thereby find suitable design of power components and array network. The methodology is intended to allow studies on any configuration of the wind power collection, regardless of choice of converter topology, array cable configuration, and control design. To facilitate harmonic susceptibility study, modelling DC collection network includes creating the harmonic model of the DC turbine converter and modelling the array network. The current harmonics within the DC collection network are obtained in the frequency domain to identify the resonance frequency of the array network and potential voltage amplification issues, where the harmonic model of the turbine converter is verified by the comparison of the converter switching model in the PLECS™ circuit simulation tool and laboratory test bench, and show a good agreement.

Harmonic Susceptibility Study of DC Collection Network Based on Frequency Scan and Discrete Time-Domain Modelling Approach / Imbaquingo, C. E.; Sarra, E.; Isernia, N.; Tonellotto, A.; Chen, Y. -H.; Dincan, C. G.; Kjaer, P.; Bak, C. L.; Wang, X.. - In: JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING. - ISSN 2090-0147. - 2018:(2018), pp. 1-25. [10.1155/2018/1328736]

Harmonic Susceptibility Study of DC Collection Network Based on Frequency Scan and Discrete Time-Domain Modelling Approach

Isernia N.;
2018

Abstract

The equivalent model of offshore DC power collection network for the harmonic susceptibility study is proposed based on the discrete time-domain modelling technique and frequency scan approach in the frequency domain. The proposed methodology for modelling a power converter and a DC collection system in the frequency domain can satisfy harmonic studies of any configuration of wind farm network and thereby find suitable design of power components and array network. The methodology is intended to allow studies on any configuration of the wind power collection, regardless of choice of converter topology, array cable configuration, and control design. To facilitate harmonic susceptibility study, modelling DC collection network includes creating the harmonic model of the DC turbine converter and modelling the array network. The current harmonics within the DC collection network are obtained in the frequency domain to identify the resonance frequency of the array network and potential voltage amplification issues, where the harmonic model of the turbine converter is verified by the comparison of the converter switching model in the PLECS™ circuit simulation tool and laboratory test bench, and show a good agreement.
2018
Harmonic Susceptibility Study of DC Collection Network Based on Frequency Scan and Discrete Time-Domain Modelling Approach / Imbaquingo, C. E.; Sarra, E.; Isernia, N.; Tonellotto, A.; Chen, Y. -H.; Dincan, C. G.; Kjaer, P.; Bak, C. L.; Wang, X.. - In: JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING. - ISSN 2090-0147. - 2018:(2018), pp. 1-25. [10.1155/2018/1328736]
File in questo prodotto:
File Dimensione Formato  
Journal of Electrical and Computer Engineering - 2018 - Imbaquingo - Harmonic Susceptibility Study of DC Collection Network.pdf

accesso aperto

Licenza: Creative commons
Dimensione 792.58 kB
Formato Adobe PDF
792.58 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11588/996605
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? 0
social impact