The actual study proposes a power quality analysis of a medium-sized industrial microgrid which in turn generates harmonic disturbances on the medium voltage side of a 110kV/20kV substation. Due to the interconnection of different loads on similar medium voltage busbars, the harmonic distortion propagates along the circuit affecting the stability of the local grid. Using advanced simulation tools based on numerical analysis an equivalent circuit of the microgrid is created. According to the computed results levels of total harmonic distortion exceeding the limit values imposed by the national performance standards were discovered within the load understudy. In this regard, a complex analysis procedure targeting the variable speed drives is deployed in order to identify the proper technical solutions for attenuation and filtering of harmonics in the system. Therefore, this study highlights solutions for mitigating the higher-order harmonics and the impact of their implementation, i.e. the best solution.

A Practical Approach to Mitigate the Harmonic Distorsion in a Microgrid, Case Study / Muresan, A.; Fati, O.; Czumbil, L.; Ceclan, A.; Jurj, D. I.; Rizzo, R.; Micu, D. D.. - In: PROCEEDINGS - INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER. - ISSN 1540-6008. - 2022-:(2022), pp. 1-6. (Intervento presentato al convegno 20th International Conference on Harmonics and Quality of Power, ICHQP 2022 tenutosi a ita nel 2022) [10.1109/ICHQP53011.2022.9808785].

A Practical Approach to Mitigate the Harmonic Distorsion in a Microgrid, Case Study

Rizzo R.;
2022

Abstract

The actual study proposes a power quality analysis of a medium-sized industrial microgrid which in turn generates harmonic disturbances on the medium voltage side of a 110kV/20kV substation. Due to the interconnection of different loads on similar medium voltage busbars, the harmonic distortion propagates along the circuit affecting the stability of the local grid. Using advanced simulation tools based on numerical analysis an equivalent circuit of the microgrid is created. According to the computed results levels of total harmonic distortion exceeding the limit values imposed by the national performance standards were discovered within the load understudy. In this regard, a complex analysis procedure targeting the variable speed drives is deployed in order to identify the proper technical solutions for attenuation and filtering of harmonics in the system. Therefore, this study highlights solutions for mitigating the higher-order harmonics and the impact of their implementation, i.e. the best solution.
2022
978-1-6654-1639-9
A Practical Approach to Mitigate the Harmonic Distorsion in a Microgrid, Case Study / Muresan, A.; Fati, O.; Czumbil, L.; Ceclan, A.; Jurj, D. I.; Rizzo, R.; Micu, D. D.. - In: PROCEEDINGS - INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER. - ISSN 1540-6008. - 2022-:(2022), pp. 1-6. (Intervento presentato al convegno 20th International Conference on Harmonics and Quality of Power, ICHQP 2022 tenutosi a ita nel 2022) [10.1109/ICHQP53011.2022.9808785].
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11588/937977
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? 0
social impact