A meticulous thermo-hygrometric control is essential for various industrial production processes, particularly those involving the painting phases of body-in-white, in which the air temperature and relative humidity in production boots must be limited in strict intervals to ensure the high quality of the final product. However, traditional proportional integrative derivative (PID) controllers may result in non-optimal control strategies, leading to energy wastage due to response delays and unnecessary superheatings. In this regard, predictive models designed for control can significantly aid in achieving all the targets set by the European Union. This paper focuses on the development of a predictive model for the energy consumption of an air handling unit (AHU) used in the paint-shop area of an automotive production process. The model, developed in MATLAB 2024b, is based on mass and energy balances within each component, and phenomenological equations for heat exchangers. It enables the evaluation of thermal powers and water mass flow rates required to process an inlet air flow rate to achieve a target condition for the temperature and relative humidity. The model was calibrated and validated using experimental data of a real case study of an automotive production process, obtaining mean errors of 16% and 31% for the hot and cold heat exchangers, respectively, in predicting the water mass flow rate. Additionally, a control logic based on six regulation thermo-hygrometric zones was developed, which depended on the external conditions of temperature and relative humidity. Finally, as the main outcome, several examples are provided to demonstrate both the applicability of the developed model and its potential in optimizing energy consumption, achieving energy savings of up to 46% compared to the actual baseline control strategy, and external boundary conditions, identifying an optimal trade-off between energy saving and operation feasibility.

Physical Model for the Simulation of an Air Handling Unit Employed in an Automotive Production Process: Calibration Procedure and Potential Energy Saving / Viscito, Luca; Pelella, Francesco; Rega, Andrea; Magnea, Federico; Mauro, Gerardo Maria; Zanella, Alessandro; Mauro, Alfonso William; Bianco, Nicola. - In: ENERGIES. - ISSN 1996-1073. - 18:7(2025). [10.3390/en18071842]

Physical Model for the Simulation of an Air Handling Unit Employed in an Automotive Production Process: Calibration Procedure and Potential Energy Saving

Viscito, Luca;Pelella, Francesco;Rega, Andrea;Mauro, Gerardo Maria;Mauro, Alfonso William
;
Bianco, Nicola
2025

Abstract

A meticulous thermo-hygrometric control is essential for various industrial production processes, particularly those involving the painting phases of body-in-white, in which the air temperature and relative humidity in production boots must be limited in strict intervals to ensure the high quality of the final product. However, traditional proportional integrative derivative (PID) controllers may result in non-optimal control strategies, leading to energy wastage due to response delays and unnecessary superheatings. In this regard, predictive models designed for control can significantly aid in achieving all the targets set by the European Union. This paper focuses on the development of a predictive model for the energy consumption of an air handling unit (AHU) used in the paint-shop area of an automotive production process. The model, developed in MATLAB 2024b, is based on mass and energy balances within each component, and phenomenological equations for heat exchangers. It enables the evaluation of thermal powers and water mass flow rates required to process an inlet air flow rate to achieve a target condition for the temperature and relative humidity. The model was calibrated and validated using experimental data of a real case study of an automotive production process, obtaining mean errors of 16% and 31% for the hot and cold heat exchangers, respectively, in predicting the water mass flow rate. Additionally, a control logic based on six regulation thermo-hygrometric zones was developed, which depended on the external conditions of temperature and relative humidity. Finally, as the main outcome, several examples are provided to demonstrate both the applicability of the developed model and its potential in optimizing energy consumption, achieving energy savings of up to 46% compared to the actual baseline control strategy, and external boundary conditions, identifying an optimal trade-off between energy saving and operation feasibility.
2025
Physical Model for the Simulation of an Air Handling Unit Employed in an Automotive Production Process: Calibration Procedure and Potential Energy Saving / Viscito, Luca; Pelella, Francesco; Rega, Andrea; Magnea, Federico; Mauro, Gerardo Maria; Zanella, Alessandro; Mauro, Alfonso William; Bianco, Nicola. - In: ENERGIES. - ISSN 1996-1073. - 18:7(2025). [10.3390/en18071842]
File in questo prodotto:
File Dimensione Formato  
energies-18-01842 (1).pdf

accesso aperto

Descrizione: Full paper
Tipologia: Versione Editoriale (PDF)
Licenza: Dominio pubblico
Dimensione 5.8 MB
Formato Adobe PDF
5.8 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11588/1005476
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 3
  • ???jsp.display-item.citation.isi??? ND
social impact